Estimating Motor Life Using Motor Circuit Analysis
Predictive Measurements: Part 2 by
Howard
W Penrose, Ph.D. General Manager, ALL-TEST Pro A
Division of BJM Corp
Download a printable 72k pdf version
Abstract: In the first paper[i],
the keys to the implementation of a technology for
predictive maintenance and reliability and the ability
to estimate how much time is left prior to equipment
failure was outlined. The first part of the study was
to establish a baseline for electric motor life time
estimation using motor circuit analysis techniques was
presented. In the second part of the study, variations
of operating conditions including environment, load,
cycling, and others are evaluated to fine-tune the
estimation. The focus of the study is low voltage,
random wound machines in a variety of environments.
Additional studies are in progress for medium voltage
rotating machinery.
INTRODUCTION
Electric motor winding failure occurs over time based
upon a variety of conditions. In the first paper, the
baseline for estimating time to failure was determined
for a standard motor condition. In this paper, several
of the general causes for adjustments to the time to
failure estimations will be included.
Considerations include: Environmental conditions; Load;
Load variations; Severity of fault; Power supply
condition; and, Mechanical condition. Estimations are
based upon a survey of tested motors, and changes to
condition over time that has identified faults using
MCA. In this paper, we will review the environmental
conditions, load and load variations with the remainder
coming in following papers.
Motor Circuit Analysis (MCA) involves low voltage
measurements of resistance, impedance, inductance, phase
angle, current:frequency response and insulation to
ground testing. Winding condition is determined by
comparing similar windings, such as one phase to another
in a three phase motor, with variations identifying
defects. Resistance is used to identify loose or broken
connections, impedance and inductance are compared in
order to identify winding contamination or overheated
windings, phase angle and current:frequency are used to
identify inter-turn insulation degradation, and
insulation resistance is used to identify insulation to
ground faults.
WINDING CONTAMINATION
Winding contamination is identified by comparing the
pattern of impedance and inductance. Impedance will
decrease, and fall towards inductance, as the insulation
system begins to degrade due to contamination. However,
in most cases, the insulation life may be extended by
removing from service, cleaning, dipping and baking
(re-insulating) for a limited time after detection. As
the fault progresses, it will graduate to an insulation
to ground fault or winding short. The progress is,
normally, insulation degradation, changes to phase angle
or I/F, then failure.
Table 1: Winding Contamination Rating to Hours (example)

The
ambient environment effects the progression of winding
contamination degradation. Table 1 identifies a rating
system applied to the detection of winding contamination
when testing monthly (see table in Paper 1).
Statistically, it was found that the mean time to
failure after fault detection progressed by a simple
natural log multiplier:
Equation 1: Winding Contamination Multiplier
e-m
* Hb
where m = multiplier and Hb = Base Hours
The
multiplier was based upon the ambient conditions (See
Table 2) and the base hours on the base rating tables in
Paper 1.
Table 2: Ambient Conditions
|
Condition |
m |
Description |
|
1 |
0 |
Clean and dry. Ambient temperature < 25C. |
|
2 |
0.5 |
Clean factory environment. Conditioned air with
ambient temperature < 25C (ie: Assembly plants) |
|
3 |
0.75 |
Medium factory environment. Variable ambient
temperatures and humidity. |
|
4 |
1 |
Harsh factory environment. Variable ambient
temperatures and humidity. Enclosed motors in
exterior environments. |
|
5 |
N/A |
Harsh environment. High humidity, high ambient
and/or Acidic/basic environment. Includes motors
mounted in cooling towers. |
WINDING SHORTS
A
variety of conditions effect the time to failure
following the detection of winding shorts.
Statistically, the variations in time to failure
followed a simple logarithmic scale. The dominant
conditions include, for the purpose of this paper:
ü
Motor loading
ü
Start/Stop cycling
Equation 2: Log Scale Used
M =
e-b
Where M = multiplier and b = condition variable
Motor Loading
In
Paper 1, the load was based upon an average of 75%.
Conditions vary, depending upon the application of the
electric motor. For instance, many fan and pump
applications are only loaded to about 50% of load. In
other cases, the manufacturer may have included the
service factor in the design of the equipment. The
average motors evaluated were NEMA Design B, 1.15
service factor, TEFC.
Table 3 indicates the condition variable value applied
to Equation 2 for motor loading. For instance, if a
motor is loaded at 25% of nameplate rating, the
resulting multiplier (ML) would be ML
= e-(-0.5) = 1.64.
Table 3: Load Conditions (Condition Variables)
|
Load |
Condition Variable (b) |
|
25% |
-0.5 |
|
50% |
-0.25 |
|
75% |
0 |
|
100% |
0.75 |
|
115% |
2 |
|
>115% |
N/A (immediate failure) |
Motor Start/Stop Cycling
The
number of starts and stops that a motor is capable of
sustaining in an hour is primarily based upon the rotor
design. In the case of estimating time to failure, the
start/stop frequency is based upon the stresses to the
winding, both mechanically and electrically. The
majority of motors reviewed in this survey were random
wound. While the impact did appear to vary by motor
size, for time and simplicity, we will consider a
conservative cycling at 50 horsepower in an across the
line starting condition.
Table 4: Start/Stop
|
Number Start/Stops per hour (average) |
Condition Variable (b) |
|
0.25 |
0.25 |
|
0.5 |
0.75 |
|
1 |
1 |
|
2 |
1.5 |
|
4+ |
2 |
Other Conditions
A
variety of other conditions exist that create variations
in the time to failure estimation. These conditions
will be included in future papers.
Winding Short Multiplier
Using the days/hours found in Paper 1 as the base system
(1 year = 4000 hours), an estimated time to failure can
be calculated.
Equation 3: Winding Short Formula
M =
ML * MS * Hours
Where ML is the Motor Loading multiplier and
MS is the Motor Starting/Stopping multiplier.
Using this algorithm, a time estimation can be
considered for trended equipment, in various loads and
stop/start cycling environments, that has identified
winding shorts using MCA.
TEST
CASES
Following are several test cases using the system
described in this paper.
Winding Contamination (10 horsepower)
A 10
horsepower motor in a plywood application (screen
motor), operating 6,000 hours per year in a damp
environment tested monthly. Winding contamination
indicated in February of 2003. Applied a condition of 3
from Table 2.
Monthly time to failure estimation from Figure 1 of the
first time to failure paper shows a potential life of
2000 hours. Applied to Equation 1, the estimated life
of this application was:
Example 1: Winding Contamination
e-0.75
* 2000 = 945 hours
The
motor was removed, cleaned, dipped and baked during the
following month. Winding contamination was visually
confirmed.
Winding Short (150 horsepower)
A
150 horsepower motor in a paperboard application tested
quarterly. A turn to turn short developed with both
phase angle and I/F changing by more than 3 points
between tests. The motor is started and stopped
approximately twice per hour and is running at about 50%
load. The motor had been tripping off-line randomly.
Operates 4,000 hours per year. The base hours, from
Table 3 of Paper 1 show 335 hours as a baseline.
Example 2: Winding Short
e-(-0.25)
* e-1.5 * 335 hours = 96 hours
The
effective time to failure was estimated to occur in just
over 1 week. The motor catastrophically failed in
operation within 3 weeks.
Winding Contamination (100 horsepower)
Winding contamination detected in a 100 horsepower motor
which is tested every six months. The motor operates
2,000 hours per year and the insulation resistance
dropped to 45 MegOhms. Ambient conditions indicated a
condition 2 environment.
Example 3: Winding Contamination
e-0.5
* 1,000 hours = 606 hours
The
motor remained in operation for close to one year prior
to being removed for rewind repair.
CONCLUSION
Time
estimation of electric motor life following the
detection of winding contamination or developing shorts,
using motor circuit analysis measurements of resistance,
impedance, inductance, phase angle, current/frequency
response and insulation to ground can be performed.
Evaluation must be based upon averages with multipliers
that indicate operating conditions.
The
purpose of the estimation is to allow the diagnostic
user to plan shutdowns, repairs and/or replacements.
The estimation should be considered as the average time
to failure and any action should be taken well within
the estimated period.
Additional work on low and medium voltage electric
motors continues based upon real-world research and
development and equipment history. Uses of these
formulae are at the risk of the user.
ABOUT THE AUTHOR
Dr
Penrose is the General Manager of ALL-TEST Pro, A
Division of BJM Corp. BJM Corp is a manufacturer of
motor circuit analysis instruments and electrical
submersible pumps. Dr Penrose is presently the Vice
Chair of the Connecticut Section of IEEE and holds other
elected and volunteer offices with IEEE and other
professional organizations.
Contact:
Howard W Penrose, Ph.D.
General Manager, ALL-TEST Pro
A Division of BJM Corp
123
Spencer Plain Rd
Old
Saybrook, CT 06475
Ph: 860 399-5937 ext 123
Fax: 860 399-3180
Email:
hpenrose@alltestpro.com
Web:
www.alltestpro.com
Cell: 860 575-3087
ACKNOWLEDGEMENTS
A
large number of motor circuit analysis users submitted
tens of thousands of sets of data, findings and history
as part of these studies.
BIBLIOGRAPHY
Penrose, Howard W, Ph.D., “Estimating Motor Life Using
Motor Circuit Analysis Measurement,” Proceedings: 2003
EIC/EMCW Conference, IEEE.
[i]
Penrose, Howard W,
Ph.D., “Estimating Motor Life Using Motor Circuit
Analysis Measurement,” Proceedings: 2003 EIC/EMCW
Conference, IEEE.
|