by
E.
Wiedenbrug SM IEEE, G. Frey M IEEE, J. Wilson, M IEEE
Baker Instrument Company
engr@bakerinst.com
Click here for a print friendly 165k pdf version
Abstract:
Impulse
testing is an integral part of predictive maintenance
of electrical motors. Through the following questions
the influence that extensive impulse testing has on a
motor is investigated. Can impulse testing damage
healthy or deteriorated insulation? Can DC
Resistance, Inductance, Megger or HiPot tests diagnose
weak turn-to-turn insulation? After failing an impulse
test, are motor with weak insulation able to operate?
Are motors with a turn-turn short capable of continued
operation? This was accomplished by putting a low
voltage motor through extensive testing rigors, until
inducing a failure. Following the failure, additional
testing investigated the possible deteriorating
effects on turn-turn insulation due to impulse testing
beyond the motor’s dielectric breakdown. NOTE: This
paper was edited from the original version of the IEEE
paper published in 2003.
I.
Introduction
Unplanned
downtime of industrial processes is very expensive,
frequently with costs exceeding tens of thousands of
dollars per hour. It is crucial to utilize scheduled
plant downtime, during planned maintenance periods,
for identifying equipment likely to fail.
Identification of weak motors, and their replacement
or repair during a planned outage, is more cost
effective than the associated costs of unscheduled
plant downtime and rushed repairs.
A.
Insulation Failure Mechanisms
According
to IEEE and EPRI [1-2] studies, insulation faults are
associated with 26-36% of motor failures. D.E.
Crawford’s investigations on failure mechanisms of
motors concluded: “the great majority of failures
seemed to be associated with wire” [3]. “This results
in low power intermittent arcing which causes erosion
of the conductor until enough power is drawn to weld
them. Once welding has occurred, high induced currents
in the shorted loops lead to rapid stator failure”. He
states: “the ultimate motor failure on a motor
returned from the field may not indicate what
initiated the failure”. In short, most of the stator
failures start as turn-turn failures, rapidly
developing into catastrophic copper-ground or
phase-phase faults.
Internal
currents are induced in the motor as soon as an
insulation failure reaches a turn-turn short. “These
currents have the order of twice the blocked rotor
current”. Tallam, Habetler and Harley [4] state that
“If left undetected, turn faults can propagate,
leading to phase-ground or phase-phase faults.” The
blocked rotor currents are upwards of 6-10 times rated
current. The heating energy is proportional to I2R,
which leads to the expected 14,000% – 40,000% of rated
wattage deteriorating the insulation in the faulted
turns. A basic rule of thumb is, for every additional
10oC the winding deteriorates at twice the
rate. Excessive heating by turn-turn shorts is the
reason why faulty motors will almost always fail in a
matter of minutes if not seconds.
B.
Fundamentals of insulation testing:
The most
common field tests for ensuring insulation integrity
are:
DC coil
resistance (IEEE Std 118) [7]
Stator
inductance (no standard)
Insulation
resistance, (IEEE Std 43) [8]
HiPot
(IEEE Std 95) [9]
Polarization index (PI) ( IEEE Std 43) [8]
Impulse
test (IEEE Std 522, IEC 34-15, NEMA MG1) [4, 10, 11]
II.
Fundamentals of Impulse Testing
Impulse
testing is based on sending a voltage impulse with a
steep voltage front (high )
to the tested coil in the motor. This voltage impulse
is generated by quickly discharging a capacitor into
the windings of the motor. This steep fronted voltage
sets up a nonlinear voltage distribution in the coil
similar to the ones observed in PWM drives [12-14].
This nonlinear voltage distribution creates a
turn-turn voltage difference. By ramping the amplitude
of subsequent voltage pulses sent to the motor, the
voltage introduced between turns of the same winding
is also ramped. The energy from the capacitor that was
discharged onto the windings sets up a dampened
oscillation between the motor’s inductance L,
the capacitor C, and the system’s resistance,
R. This oscillation has an internal frequency
f according to [10] of:
(1)
Any weak
turn-turn insulation within the motor will have a low
failure voltage. While the introduced turn-turn
voltage is below failure voltage level, there will be
no current flowing through the weak insulation.
Discharge current will flow through the insulation as
soon as the introduced turn-turn voltage exceeds the
breakdown level. This discharge represents a current
path that is in parallel to the shorted windings of
the coil, and has the effect of reducing the winding’s
effective inductance.
Changes in
the effective inductance of the motor that occurs
during the internal discharge increases the frequency
of this oscillation. Impulse testing equipment
monitors the voltage trace at the coil terminals or
the terminal leads to the motor. This determines the
increase in frequency. This frequency increase is
easiest viewed by a ‘shift to the left’ of the impulse
waveform as shown in Figure 1.

Figure
1: Passed and Failed Impulse Waveforms
This shift
to the left can be very slight. For that reason it is
advisable to utilize a numeric method of observation
which allows an accurate, repeatable and unbiased
assessment. One such method is the Error to Area Ratio
(EAR). The EAR is defined as:
(2)
where F(1,2)
are the two waveforms; and i, j are
summation of the samples of the digitized waveforms.
Identical waveforms will have an EAR of 0%, while very
similar waveforms will have EAR of few percent. In a
production environment, phase-phase comparison of
impulse waveforms is commonly performed before the
motor is assembled. This allows for identifying weak
turn-turn insulation, as well as reversed coils or
different numbers of turns per phase. In PM
applications, subsequent pulses of the same winding
are compared during the ramping of the pulse voltage.
This has the advantage that the rotor position does
not influence the test, while still investigating
turn-turn insulation. An EAR of 5%, for example, is
very difficult to discern on the display, yet can be
the symptom of a failed winding.
Impulse
testing and some of the insulation deterioration
mechanisms are similar. Therefore it is of interest to
investigate whether impulse testing, as commonly
performed in Predictive Maintenance (PM), could
deteriorate insulation condition.
III.
Test
Protocol
The study
test protocol was designed to answer the questions
asked by exposing one motor to the rigors of testing.
The first test motor is a new factory 5hp 6 pole 460V
connected dual voltage Hemco Global HE EPACT Compliant
motor with a rated current of 7.7A, rated speed of
1170rpm and a 215T frame. This motor was chosen
because it was the least expensive new motor with
these ratings. The hope was that the least expensive
motor gave a lower average in insulation quality. In
order to have a baseline reading of all tests, the
motor was tested prior to starting the study.
Table 1: Testing New Motor
|
DC Resistance |
Phase 1-2:
1.88
Phase 2-3:
1.78
Phase 3-1:
1.88 |
|
Insulation
Resistance |
20 GΩ |
|
HiPot |
Pass |
|
Impulse |
1-2% >=2kV |
The first
question, whether impulse testing damages healthy
windings, was investigated by exposing the motor to 3
million impulses at the suggested 2kV voltage level.
To perform a normal test, modern impulse testers ramp
each phase of a 460V winding with approximately 80
impulses of voltage levels increasing from 0V to 2kV.
A very intensive PM program will test each motor up to
twice a year for turn-turn insulation quality. This
frequency of testing would expose a motor to a total
of 3 million pulses (one million per phase) only after
the motor was in operation for over 6,200 years.
DC
resistance per phase, insulation resistance, HiPot and
Impulse test including EAR were recorded prior to each
set of 3 million impulses. The PI test was not
performed because IEEE 43 suggests no useful PI
information will be obtained by testing such small
motors.
Table 2: Results from Suggested Test Voltage Level
|
|
Results |
|
DC Resistance |
Phase1-2:
1.88
Phase2-3:
1.78
Phase 3-1: 1.88 |
|
Insulation
Resistance |
20.4 G Ω |
|
HiPot |
Pass |
|
Impulse |
Pulse-Pulse
EAR: 1-2% <= 2kV |
To allow
for possible misuse of the impulse tester when
checking a motor’s turn-turn insulation, we tested the
motor, again for 3 million impulses at both, 3kV and
4kV. This represent 150% and 200% over suggested test
voltage. The same results were seen after this testing
was done.
Table 3: 150% - 200% Testing Voltage
|
DC Resistance |
Phase 1-2:
1.88
Phase 2-3:
1.78
Phase 3-1:
1.88 |
|
Insulation
Resistance |
20 GΩ |
|
HiPot |
Pass |
|
Impulse |
1-2% >=4kV |
Since the
question whether impulse testing deteriorates already
damaged insulation needed evaluation too, we
manufactured a weakness within the insulation. This
was achieved by repeating the 3 million impulses at
successive 1kV increased levels, until failure
occurred. This failure took place at a 7kV level, or
350% over the recommended test voltage. After failure,
subsequent impulse tests showed the punctured
insulation to have a breakdown voltage of 1700V.
Again, we recorded DC resistance, Insulation
Resistance, HiPot values and EAR.
Table 4: Results of Testing After Applied Weakness
|
|
Results |
|
DC Resistance |
Phase 1-2:
1.88
Phase 2-3:
1.78
Phase 3-1:
1.88 |
|
Insulation
Resistance |
20.4 GΩ |
|
HiPot |
Pass |
|
Impulse |
20% > 1.7kV |
In order
to investigate whether impulse testing further damages
already damaged insulation, an additional 20 million
impulses were performed on the failed phase at voltage
levels above failing voltage level. The attempt here
was to further deteriorate the motor and try to induce
a lower failure voltage level. After concluding this
additional testing, DC resistance, insulation
resistance, HiPot and EAR were recorded.
To assess
whether a motor that has failed the impulse test is
still capable of running, we performed repeated starts
on this motor. During this process we monitored
voltage spikes on phase A (the failed phase)
which happened during the closing and the opening of
the breaker process. A Tektronix TDS360 Oscilloscope
captured the traces utilizing a Tektronix P6015A High
Voltage Probe. Steady state operation was recorded
with Fluke 77 multimeters and clamp-on probes.
The motor
withstood 42 starts and stops, running under normal
operation after each one of these starts. On the 43rd
start the motor started to sound louder, like an
overloaded transformer. Within 40 seconds data was
taken on the stator currents. Motor operation was
stopped due to the amount of smoke released by the
motor, and the fire hazard. The currents prior to the
turn-turn short were balanced, 7.2A per phase. The
stator currents during the 40 seconds of operation
with the turn-turn short were: Phase A = 11.9A;
Phase B = 8.3A; Phase C = 7.2A.
After
finishing these tests, we measured once more the DC
resistance, insulation resistance, HiPot and EARs.
Table 5: After Short Turn
|
DC Resistance |
Phase 1-2:
1.85
Phase 2-3:
1.78
Phase 3-1:
1.78 |
|
Insulation
Resistance |
20 GΩ |
|
HiPot |
Pass |
|
Impulse |
25% any voltage |
IV.
Results
The
testing is divided into four segments:
Prior to
test: The motor is in mint condition
Prior to
impulse failure: The motor has withstood over 20
million impulses ranging from 100% rated testing
voltage to 300% rated testing voltage without breaking
down.
Prior to
shorted failure: The motor has been exposed to
additional 20 million impulses above the 1700V
breakdown voltage.
After
shorted turn-turn: The motor has started, ran and
stopped 42 times without noticeable deterioration, and
additionally started a 43rd time with a
shorted turn-turn fault. It ran less than 40 seconds
in this condition, during which it released smoke, and
was stopped due to fire hazard.
Table 6: Complete Results
|
|
Baseline |
2kV Test
Voltage |
3-4kV Test
Voltage |
Introduced
Weakness |
Post 43 Starts
& Stops |
|
DC Resistance
Phase 1-2
Phase 2-3
Phase 3-1 |
1.88
1.78
1.88 |
1.88
1.78
1.88 |
1.88
1.78
1.88 |
1.88
1.78
1.88 |
1.85
1.78
1.78 |
|
Insulation
Resistance |
20.4 GΩ |
20.4 GΩ |
20.4 GΩ |
20.4 GΩ |
20 GΩ |
|
HiPot |
Pass |
Pass |
Pass |
Pass |
Pass |
|
Impulse
(Pulse-Pulse EAR) |
1-2% <=2kV |
1-2% <=4kV |
1-2%<=2kV |
20% >1.7kV |
25% any Voltage |
A. DC
Resistance Values:
All
resistance values remained constant per phase until the
shorted turn-turn failure occurred. The stator
resistance showed no difference from the impulse
testing, neither before nor after the insulation was
broken down. The DC resistance test is a low voltage
test that checks the copper of the stator windings. It
does not offer predictive maintenance value for
turn-turn insulation.
B.
Insulation Resistance:
Insulation
resistance values of the winding at the different stages
of testing were obtained with 500V DC test voltage.
The copper-ground insulation
resistance remained constant throughout the test until
the shorted turn-turn condition was established, and
parts of the windings were heated up beyond the release
of smoke. Until the shorted turn-turn currents caused
excessive heat, the Insulation Resistance offered no
sign that pointed to possible winding deterioration.
After cooling down, the copper-ground resistance dropped
by 400 MW.
C.
HiPot:
The HiPot
test passed at every instance. After completion of all
other testing, the HiPot failure voltage level was found
to be 3040V. This relatively low voltage level can best
be explained by the damage of the copper-ground
insulation that the excessive heat caused during the
turn-turn insulation.
D.
Impulse
Testing:
The impulse
test shows a consistent low EAR value for winding in
good condition. Once the winding shows poor turn-turn
condition, the value jumped up significantly, yet the
motor was still operational.
2kV is the
common voltage level for PM testing of 460V motors.
Table V shows the number of pulses and their associated
voltage level withstood by the motor previous to
failure:
Table 2:
Voltage Level, % Rating, # of Pulses, Cumulative Years
of Intensive PM Testing
|
Voltage
Level |
% rated |
Impulses |
Cumulative
years |
|
2,000V |
100% |
3,276,000 |
6,825 |
|
3,000V |
150% |
3,536,000 |
14,191 |
|
4,000V |
200% |
4,536,000 |
23,642 |
|
5,000V |
250% |
3,546,000 |
31,029 |
|
6,000V |
300% |
5,175,000 |
41,810 |
The healthy
motor’s winding saw a minimum of over 3 million impulses
at each of the five voltage levels. The total number of
impulses adds to more than 20 million. Normally, a 480V
motor sees 80 impulses per phase per test using the
computerized ramp rate. Testing a motor twice a year
leads to a total of 480 impulses between 0V and 2kV. In
order for a normal motor to see 20 million impulses due
to testing, it would need to operate an equivalent of
over 41,000 years with a consistent aggressive
maintenance schedule. In addition to this very
unreasonable number of pulses that the tested motor saw,
their average size was of two to three times recommended
amplitude.
This
absolutely unrealistic rough testing performed on the
motor did not cause any noticeable deterioration on the
winding until the voltage level of the test was elevated
to 7kV, or 350% rated testing voltage level.
The EAR
remained constantly low during all the previous testing,
between 1% and 2%.
The impulse
wave shape and the EAR changed only after the insulation
broke down. The breakdown lowered the passing voltage
level to 1,700V. Any voltage above that caused the EAR
to be 20%; while any voltage below this kept the winding
from discharging turn-turn with an EAR of 1%.
The
additional 20 million impulses that were sent to the
motor above the new 1700V breakdown voltage level, did
not change the breakdown inception. The breakdown
voltage level remained at 1700V even after 20 million
discharges. It was not possible to alter the discharge
inception voltage by forcing an unrealistic large amount
of discharges in the weakened insulation.
E.
Start and
Stop stress test:
D.E.
Crawford [3] verified the hypothesis of wire-wire motion
during startup by using high-speed filming. Weak
insulation needs less stress to failure than healthy
insulation. B.K. Gupta et al [15] monitored surge
transients in power systems. They conclude that opening
of breakers, but also their closing, cause voltage
surges in the system.
In order to
further stress the motor, it was subject to multiple
starts and stops. Monitoring of phase A voltage
with a scope and triggering for surges delivered a
number of events where the motor was exposed to
transient voltage spikes induced by the operation of the
breaker. Compared to startup of a motor, an impulse
tester’s energy delivered to the winding is very limited
and controlled. It does not suffice to set the windings
in motion and have them rub against each other. The
rubbing of the windings against each other can cause a
turn-turn short, and the potentially available energy
feeding into the fault is limited only by the
over-current protection of the motor. Catastrophic
failures are a natural consequence.
 
Figure 3-4:
Startup and turnoff voltage surge.
Figures 3
and 4 show voltage surges that were captured during
starting and stopping of the motor. The stresses
introduced into the winding during startup and stopping
process were twofold: rubbing of wires against each
other, and voltage surges coming from the power system.
These stresses were the cause of the shorted turn-turn.
V.
Conclusions
Very
extensive impulse testing of a 5hp, followed by multiple
starts and stops under normal line conditions and high
load and excessive startup testing of a 1hp motor lead
to the following conclusions:
Exaggerated
amounts of impulse testing performed on rated impulse
testing levels did not break down healthy insulation of
the motor. Increasing the voltage levels to 150%, 200%,
and even 250% and 300% while exposing the motor to
excessive pulses, did not break down the insulation.
Weakened
insulation, tested at voltage levels above breakdown
showed no additional signs of deterioration, even after
extreme repetitions of discharges in the weak
insulation.
The weakened
insulation could not be detected neither by DC
resistance readings, nor by Insulation Resistance
(Megger), nor by HiPot measurements. The only reliable
test showing the weakness of the insulation prior to a
turn-turn short was the impulse test.
The motor
with the weak insulation was very capable to run steady
state. It also withstood multiple starts and stops. One
of these starts caused the motor to have a turn-turn
short.
The motor
smoked within a minute of having a turn-turn short and
running under a normal load condition, confirming the
very rapid development of a catastrophic failure to the
motor once the turn-turn fault occurred.
DC
resistance were capable of finding the fault only after
it had occurred. Finding a shorted turn-turn fault has
little, if any value from a predictive standpoint, since
the motor typically fails within few minutes if not only
seconds of the short, as confirmed in the test series.
VI.
References
[1] “Report
of Large Motor Reliability Survey of Industrial and
Commercial Installations”, Parts I and II, Motor
Reliability Working Group, IEEE IAS Transactions Vol
IA-21, No. 4, pp. 863, 1985.
[2]
“Improved Motors for Utility Applications”, EPRI
EL-4286, Vol. 1&2, pp 1763, 1982.
[3] D.E.
Crawford, “A Mechanism of Motor Failures”, IEEE 1975.
[4] “Impulse
Voltage Withstand Levels of Rotating a.c. Machines with
Form-Wound Stator Coils”, IEC 34-15, 1995.
[5] J.A.
Oliver, “Electric Motor Predictive and Preventive
Maintenance Guide”, EPRI NP-7502s, 1992.
[6] N.K.
Ghai, “Design and Application Considerations for Motors
in Steep-Fronted Surge Environments”, IEEE IAS
Transactions, Vol. 33, No. 1, 1997, pp 177.
[7] “IEEE
Standard Test Code for Resistance Measurement”, IEEE Std
118-1978.
[8] “IEEE
Recommended Practice for Testing Insulation Resistance
of Rotating Machinery”, IEEE Std 43-2000.
[9] “IEEE
Recommended Practice for Insulation Testing of Large AC
Rotating Machinery with High Direct Voltage”, ANSI/IEEE
Std 95-1977.
[10] “IEEE
Guide for Testing Turn-to-Turn Insulation on Form-Wound
Stator Coils for Alternating-Current Rotating Electric
Machines”, IEEE Standards Board, IEEE Std 522-1992.
[11]NEMA,
“Motors and Generators”, NEMA Standards Publication No.
MG1-1998.
[12] M.
Melfi, J. Sung, S. Bell, G. Skibinski, “Effect of Surge
Voltage Risetime on the Insulation of Low Voltage
Machines Fed by PWM Converters”, IEEE IAS Conference,
1997, pp. 5_7.
[13]Y. Tang,
“Analysis of Steep-Fronted Voltage Distribution and Turn
Insulation Failure in Inverter Fed AC Motor”, IEEE IAS
Conference, 1997, pp. 11_6.
[14] H.A.
Toliyat, G. Suresh, A. Abur, “Simulation of Voltage
Stress on Inverter Fed Induction Motor Winding Supplied
through Feeder Cable”, IEEE IAS Conference, 1997, pp.
3_7.
[15]B.K.
Gupta, B.A. Lloyd, G.C. Stone, S.R. Campbell, D.K.
Sharma, N.E. Nilsson, “Turn Insulation Capability of
Large AC Motors. Part 1 – Surge Monitoring”, IEEE
Transactions on Energy Conversion, Vol. EC-2, No. 4,
December 1987.
[16]G.C.
Stone, S.R. Campbell, “Development of an On-line Monitor
to Measure Motor Voltage Surges”, IEEE EEIC Chicago,
1997, pp 397.
[17]NEMA MG
10-1994, “Energy Management Guide for Selection and Use
of Polyphase Motors”, National Electrical Manufacturers
Association, 1994. |