|
Modern
High Voltage Testing, with comparison to vintage High
Voltage Testing, Vs impedance based circuit
analysis/measurement (i.e. low voltage “testing”)
by George
Frey, Baker Instrument Company
Click here for a printable 94k pdf version
I. Introduction
Since the early 1980’s new
technologies have been developed that perform high
voltage evaluation of your electrical rotating
machinery. Prior to this development, high voltage test
equipment was primarily manually controlled, and thus
subject to miss-application by untrained or uncertified
personnel. Through necessity high voltage equipment
vendors needed to warn users of the potential for
incorrectly performed testing. As technology developed
and improved, the already small risk to rotating
machinery became minimized even further. As marketing
forces became aware of the technological advances, it
became necessary to discuss why the critical difference
between pre-1980’s equipment, modern equipment, and
impedance based circuit analysis (low voltage testing)
exists.
This paper discusses the
differences between manually controlled high voltage
testing, modern microprocessor controller high voltage
test techniques and impedance based circuit analysis.
For de-energized circuit analysis, modern high voltage
testing is used to detect: incipient cable faults,
winding faults, both to earth and turn to turn, winding
contamination and partial discharge’s between turns and
to earth. This is done with low energy, high voltage
impulses, microprocessor controlled with instantaneous
fault detection.
II. Modern High Voltage
Technology
Modern techniques of high voltage testing are designed
and standardized to evaluate the electrical health of an
entire electric motor system. This includes the ability
to test from the motor control center, the feeder cable
run, the windings and the rotor or armature of the AC or
DC rotating machine. This means the tests are capable of
detecting and locating incipient: cable faults, winding
faults, insulation to ground faults, motor contamination
and other problems such as leaking check valves located
in the driven load.
The advances in high voltage
testing since the 1980’s have been many. Modern high
voltage testers use modern high speed electronic
evaluation of changes to resistance, leakage current,
leakage current versus time, voltage, step-voltage,
Dielectric-absorption, frequency response, wave shape,
C.I.V. and more to detect faults at or under the levels
of energy exposed to the motor during operation. The
microprocessor controlled instantaneous trips allow
winding condition to be evaluated without compromising
dielectric integrity. The addition of field developed
PASS/FAIL test criteria makes the testing extremely
repeatable. One of the major advances is in solid-state
high voltage power supplies, replacing the heavy step up
transformer. This results in a large improvement to the
portability of the equipment. Every test is digitized
and compared to the previously applied pulse. If any
weakness is detected the test is instantaneously
stopped, preserving dielectric. The level of weakness is
stored for future reference, in the memory bank.
Ten’s of thousands of
critical motors, in actual applications, continue to be
evaluated, yearly, at over 5000 industrial locations
around the world. As opposed to studies where a few
dozen motors are currently being evaluated, this data
has already provided meaningful trending results. These
trends correspond to field studies of rotating machine
failure rates. The time required for motor failure has
already been known for many years, with a study
performed jointly by Baker Instrument Company and Owens
Corning during the 1980’s.


“Studies have shown that
many motor failures begin as turn-to-turn shorts within
a single winding. These turn-to-turn shorts then create
hot spots which in turn degenerate the insulation in
adjacent turns until the entire winding fails. The
mechanism of this type of failure may take three to six
months, or more, depending upon the operating parameters
of the motor”.
The following statement,
made in 1985 was certainly predictive!
“Improvements in surge test
equipment will include automatic test evaluation and
interruption to obviate operator interpretation and the
risk of damage. Development work is under way to
demonstrate the feasibility of computer control of such
a device”.
III. Vintage 1980’s high
voltage technology
Back in those days, there
was no way for an operator of a 1980’s style tester to
guarantee motor dielectric after a fault was detected.
Fortunately - technology has changed since then. A 1980
vintage tester was completely manually controlled, and
simply incapable of providing an instantaneous trip. In
other words, the operator was ENTIRELY responsible, both
to perform the test to the correct voltages and then
interpret the results. He simply could not release the
switch fast enough to react, even if he cared to!
The 1980’s vintage
technology surge comparison tester was (and is still)
used as a Q.C. tool to detect and diagnose many winding
faults. For example: incorrect winding connection, turn
to turn insulation integrity, phase to phase insulation
integrity, incorrect turns count, backwards coil groups.
The better 1980’s vintage surge tester’s manufactured by
Baker Instrument Company included a DC HiPot function,
which is used to verify the status of the insulation to
ground.
The design of the testers of
this era was limited by the technology available at the
time. For example, the commonly used LCD display of 2003
did not exist in 1983, making the use of phosphor CRT
technology for display a prominent design consideration.
Since the display technology available in that era was
not capable of making a persistent display appear, high
frequency surge pulse application was required. In those
days, 60 or more surges per second were required simply
to refresh the phosphor CRT.


Sometimes described as
“High Frequency Surge Testers” they apply 60 surges per
second to the winding. The surges are generated by
large, heavy step up transformers and variable
transformer to manually control the tests. These
machines are certainly effective at what they do, by
brute force application of high voltage, with no
instantaneous fault detection capability, and no current
limits. If a coil or motor passes the test, quality is
assured. If a coil or motor fails this type of test, due
to the lack of instantaneous trips, current limits and
need for operator intervention - damage may possibly
occur.
A good analogy is operating
a motor vehicle. Safe operation requires the avoidance
of other vehicles, following speed limits and minor
items such as driver intervention to stop at a red
light.
Properly performed high
voltage testing by trained personnel presents a minimal
risk to rotating equipment, just as properly performed
operation of a motor vehicle presents minimal risk to
driver safety.
IV. Are impedance based
circuit analysis/measurements (i.e. low voltage
“testing”) predictive?
Webster’s Collegiate
Dictionary defines prediction thus:
Main
Entry: pre·dict

Pronunciation:
pri-'dikt
Function: verb
Etymology: Latin praedictus, past participle of
praedicere, from prae- pre- + dicere
to say -- more at
DICTION
Date: circa 1632
transitive senses : to declare or
indicate in advance; especially :
foretell on the basis of
observation, experience, or scientific reason.
One
of the recently made claims in the marketplace is that
low voltage impedance based measurements, i.e. “tests”
are now miraculously capable of making predictive
measurements of high voltage insulators. The marketer
claims that this is now available because of sudden, new
technological breakthroughs. These measurements are
reported to be able to proof any and all rotating
machines as fit for continued service.
“Results can be found
in motors from fractional to over 10,000 horsepower”.
The marketer discusses his
predictive findings about motor insulation life in the
form of a refereed paper presented at the EIC/EMCW
conference 2003. According to this paper:
“The insulation
between conductors is stressed, causing a change to the
resistive and capacitive values of the insulation at the
fault point. High temperatures and similar reactive
faults result in carbonization of the insulation at that
point”.
The wording of this
statement is very similar to the findings published by
Baker Instrument Company nearly 20 years ago!
It also reveals the
winding must already have a copper-to-copper fault
present to generate I2R losses at the fault point,
before the impedance measurement can detect it. It is
the gross overheating of the shorted turn conductor, due
to autotransformer effect that carbonizes the
insulation.
The marketer then reveals
that the studies do not include any medium or high
voltage apparatus of any type:
“The motors covered by
this paper will include low voltage (<600 Vac), standard
integral three phase motors, operating an average of
4000 hours per year”.
Therefore, how can this
technology make a meaningful predictive analysis of
medium and high voltage rotating equipment?
V. Is Modern High Voltage
Testing Destructive?
A published survey (2001) of
utilities routinely performing High Voltage testing was
the source of this information:
“Does HiPot testing
damage a good winding? This question is raised many
times, most often by managers, who have to approve the
tests. The answer is a resounding NO. HiPot tests do not
introduce any significant degradations in a machine with
a good insulation system. Machines that have failed a
HiPot test have ALWAYS revealed poor insulation systems
upon later examination.”
Modern High Voltage test
equipment has many built in instantaneous trips, which
simply did not exist 20 years ago. As an example, the
over-current trip function of modern Baker Instrument
Company equipment can be activated with less than 1
micro-amp of leakage current.
The Maintenance Engineering
Handbook 6th edition 2002 is even more
descriptive:
“The surge test is a method
for evaluating turn-to-turn insulation within the coils.
THIS IS A NON DESTRUCTIVE TEST which indicates shorts
and dissymmetries such as incorrect number of turns in a
given coil”.
The new P – P Error Area
Ratio analysis algorithm can reliably detect the
slightest wave shape discrepancies and is capable of
tripping the tester off even before turn-to-turn
conduction can occur. The P – P EAR analysis looks at
the tiny differences in the wave, and is capable of
detecting partial discharge activity between insulated
conductors.
The Meg-Ohm test is
configured with instantaneous trip protection,
preventing the continued application of further tests
once compromised insulation has been detected. The
Dielectric Absorption, Stepped DC, Continuous Ramp, and
the HiPot tests are microprocessor controlled, which
minimizes the possibility of any test error. If
instability exists in the insulation system, the
automated test will conclude with a user safety
discharge period.
“Direct voltage
over-potential testing is generally considered a
controlled, NON-DESTRUCTIVE test in that an operator,
utilizing a suitable test set can often detect marginal
insulation from the behavior of measured current. It is
therefore possible, in many cases to detect questionable
insulation and plan for replacement without actually
breaking it down under test”
When a weak rotating machine
has been identified using these techniques, there is a
window available where a minor overhaul such as a clean
dip and bake, will restore much of the integrity of the
insulation system. However, this cost savings
opportunity could be lost if the motor is kept in
service until insulation to ground failure. When
insulation fails to ground, the core components of the
motor could be irrevocably damaged, a fact well known to
EASA:
“It may be unwise to repair
motors with catastrophic damage since there could be a
reduction in efficiency. The customer’s operational
needs, however, may necessitate the repair even though
he is aware that there may be a reduction in efficiency”
The reduction of efficiency
will then increase the operational lifetime energy
requirement. Without predictive testing methods, it may
simply have been a more cost effective choice to replace
the motor, though the initial replacement cost (instead
of repair) is greater.
VI. Capability comparison
of Surge Testing and impedance based circuit
analysis/measurements (i.e. low voltage “testing”)
Many operators of electric
motors are successfully using the technology refined in
the last 20 years to improve the reliability of their
electric motors, and beyond that, plant productivity.
Modern surge testing is used to evaluate the integrity
of the turn-to-turn and phase-to-phase insulation, and
is proven to give advance warning of impending motor
failure. Due to the low energy levels involved, the
applied power is not capable of carbonizing motor
insulation, or welding copper. Motor life remains, and
time is now available for competent repair or
replacement of the machine. Since the fault was detected
before the insulation to ground was compromised, major
repair jobs are now just minor overhauls.
Some misinformation
exists about the method that Baker Instrument Company
uses to perform the surge test. Baker Instrument Company
uses a conducted surge test method, where the surge
generator internal to the tester is connected directly
to the terminals of the winding. (Therefore, the method
detailed in IEEE Std 389-1996 recommended practice for
testing electronics transformers and inductors sec.
5.3.2 is not applicable).
All Baker Instrument
Company equipment adheres to the guidelines given by
IEEE Std 522-1992.
Impedance based circuit
analysis/measurements (i.e. low voltage “testing”) have
successfully evaluated windings that were deliberately
sabotaged. A marketer of this type of equipment
published data regarding this treatment. The damage
consisted of manipulating a single turn fault into a 2.5
horsepower electric motor as described:
“A single turn fault
was induced in a 2.5 horsepower electric motor by
raising two conductors and scratching the wire. The
wires were then placed that the surge would not detect
them until an impressed voltage of 1,750 V was reached”.
Deliberate sabotage is
certainly an effective method of causing premature
failures in electric motors. The author did not provide
any information about the ability of the surge test to
detect the problem before the scratched wires were
manipulated.
The measurements obtained
with the impedance based circuit analysis/measurement
before and after winding manipulation, showed difference
percentages of approximately 2%.
“However, surge
testing does allow for the detection of turn to turn and
coil to coil faults in most electric motors”
When the surge test
was used to diagnose insulation integrity in a 5 HP
electric motor, the numerical difference percentages
obtained against weak insulation was approximately 20%,
clearly a much larger error value. Interestingly enough,
this data was obtained at a very similar test voltage,
with a Baker Instrument Company test set. This proves
the high degree of discrimination obtained with the
test.
The fact modern high voltage
test equipment provides numerical quantification to the
waves, removes the subjectivity of analysis.
Studies of rotating machines
in the field reveal that most turn-to-turn stress is
located in the end turns of the motor. These fast rise
time transients are present in across the line
applications due to load switching and atmospheric
discharge (Lightning strikes).
They are also present when
variable frequency drives are used, due to the improved
switching efficiency of modern semiconductors, very fast
rise-time voltage spikes are developed across the motor
windings. For example:
“Eventually, an
ionized electrical path develops which allows electrical
stresses (fast rise time spikes) to cross the boundary
and short. The tendency is for a few turns to short in
the end turns of the motor windings”.
Armed with this important
information, we can make the following statements:
A)
Motor winding end turns are
where most of the electrical stress develops. It is
therefore critically important to test the insulation of
these end turns with a meaningful voltage stress.
B)
Slow rise time transients or
low voltage cannot cross this boundary, giving little to
no electrical stress at these locations in the winding.
The surge test is the only
known method where instantaneous turn-to-turn voltage
can be developed across conductors and monitored in a
controlled manner. It is commonly accepted that surge
testing is most useful for detecting faults in the end
turns.
At the EPRI Advanced
Electric Motor Predictive Maintenance Project 2003, even
a fault deliberately inserted at the midpoint of the
winding was directly detected.
Impedance based circuit analysis/measurements (i.e. low
voltage “testing”) are by their very nature completely
incapable of providing any warning of impending
insulation failure without pre-existing measurement
data.
VII. Conclusions
Surge testing detects faults
in most types of windings, with absolutely no limitation
to <600 Vac motor application.
Vintage 1980’s style high
voltage testing remains a meaningful test, and in the
hands of an experienced, trained operator will continue
to provide meaningful test results.
Impedance based circuit
analysis/measurements (i.e. low voltage “testing”) do
not allow any meaningful conclusions to be drawn about
the service capability of high voltage insulation. They
appear able to “predict” faults that are deliberately
inserted into low voltage <600Vac windings, with a low
degree of certainty. Impedance based circuit
analysis/measurements appear entirely limited to low
voltage applications, and offer no miraculous, newfound,
predictive capability.
IEEE Transaction on Industry applications, Vol38,
No3 May/June 2002
Habertler,
Tallam, Hartley. “Transient Model for Induction
Machines With Stator Winding Turn Faults”
Bonnet, Austin, “THE RESULTS ARE IN: MOTOR REPAIR’S
IMPACT ON
IEEE Std 389-1996 Section 5.3.2
|