|
Electrical Motor Diagnostics for Generators
Part 2 – Case Studies
ALL-TEST
Pro, LLC
Introduction
In Part 1 of this 3 Part
series, the basic principles of Motor Circuit Analysis (MCA) and
Electrical Signature Analysis (ESA), and how they relate to
turbine and salient-pole generators was discussed. In Part 2,
we shall discuss case studies related to marine generators and
wind turbine generators. These cases shall discuss both
generators in poor condition and in good condition. Following
Part 2, Part 3 shall discuss the details of how these analysis
were performed, including how condemning criteria was
formulated.
Case #1: Marine Salient-Pole Generator, Insulation Failure
A marine generator on board a military vessel was experiencing
increasing over-air-temperature faults during operation. These
occurred within 24 hours of operation and gradually worked
towards occurring every 6 hours of operation during the course
of eight months. The engine and cooling temperatures were
evaluated and found to be operating satisfactorily.

The generator had been installed on the vessel following
eighteen years of storage in an uncontrolled environment. It
was determined that Electrical Motor Diagnostics (EMD) would be
used to evaluate the condition of the system.
Testing was performed at the switchgear using MCA. The first
set of data identified a problem in the circuit (Table 1). A
second set of tests were performed in the connection box at the
generator (Table 2) which identified both a winding short and
poor insulation condition (unmatched Z and L).

As it requires removal of the generator through a hole in the
hull of the ship, additional testing was performed using ESA
over a period of 30 minutes.

Figure 3: ESA at ‘0’ Minutes

Figure 4: ESA at ‘10’ Minutes

Figure 5: ESA at ‘20’ Minutes

Figure 6: ESA at ‘30’ Minutes
At the end of the ESA test period, another set of MCA data was
performed while the generator was warm (Table 3).

The reduction in insulation resistance from 750 MegOhm to 55
MegOhm indicates a temperature rise somewhere in the insulation
system of approximately 140 C.
The vessel was scheduled for work in three months following
these tests, in which the time included a cruise overseas. The
question was whether the generator would be serviceable during
this time. If not, the vessel would be unable to perform its
mission.
A review of loads and temperatures were performed along with the
data from the EMD analysis. Based upon historical references
and estimated time to failure research, it was determined that
the generator could be operated in parallel with a second
generator at 50% load, or less. Watch standers were given
instructions to observe for variations in current unbalance as
an indicator of advanced winding failure. Recommendations were
provided to the vessel’s shore engineering support group for the
storage of rotating machines and generators.
After its mission, the generator was removed for repair (Figure
7) and shipped to the contracted repair shop.

Figure 7: Generator Removal
Repair requirements included complete rewind of the stator and
rotor with approved overtime in order to meet the vessel’s
shipyard schedule. Acceptance inspections were performed at the
repair center’s site under load.

Figure 8: Acceptance ESA Test
Several details on the repair were determined during the
inspection:
1.
The lead wire was reduced in size. This increases the heat
related losses at the leads and restrict the maximum current
capability of the generator.
2.
The winding conductors were increased in size. While this
allows the generator to operate slightly cooler, it affects the
circuit enough that significant tuning was required to be able
to synchronize the generator.
3.
The rotating fields were not rewound as was determined by the
ESA analysis. This results in a reduced reliability in the life
of the generator.
Case #2: Marine Salient-Pole Generator, Poor Condition
In this generator, both MCA and ESA were performed as part of a
routine maintenance.

The MCA analysis involved positioning the rotor to a set
location and performing an analysis. A loose connection, low
insulation to ground, impedance and inductance matching and
questionable winding conditions were determined. However, as
will be discussed in Part 3, the Fi and I/F primarily are used
as trendable values unless specific procedures are followed.

Figure 9: Case 2 Generator Voltage Signature
The signature found in Figure 9 indicates a relatively good
rotor with the line frequency sidebands of the number of rotor
fields times the line frequency (in this case, 360 Hz +/- 60Hz)
with a gradually dampening set of harmonics.
Based upon these findings, coupled with a visual inspection, the
generator should be scheduled for a cleaning. It is expected
that the winding conditions (L and Z) will balance out and the
insulation resistance will improve.
Case #3: Wind Turbine Generators, Good
A common issue with wind turbine generators is the passage of
grit or dust through the generator windings causing winding
shorts, bearing problems, etc.

Figure 10: Good Readings
In figure 10, the peaks are dominant in current (upper spectra)
which is related to the load. The voltage signatures identify a
relatively low level of rotor frequency. This identifies a good
online analysis of this system.
Case #4: Wind Turbine Generators, Loose Coils

Figure 11: Loose Coils
During a routine analysis, a signature was determined as 60Hz
sidebands around the running speed times the number of stator
slots of the generator. As identified in Part 1 of this series,
this indicates ‘Stator Mechanical’ which is defined as loose
coils or a loose stator. In this case, it was determined to be,
most likely, loose coils.
Conclusion
The electrical motor diagnostics techniques of motor circuit
analysis and electrical signature analysis are uniquely adapted
for troubleshooting and trending of developing generator
electrical and mechanical problems. Used together, they can
also be used to detect potential warranty issues in new and
repaired machines prior to bringing the generators online.
Author Howard W. Penrose Ph. D
Bibliography
Penrose, Howard W, Ph.D., Motor Circuit Analysis: Theory,
Applications and Energy Analysis, SUCCESS by DESIGN
Publishing, 2001.
Penrose, Howard W, Ph.D., Motor Diagnostics 2-Day Training
Manual, ALL-TEST Pro, 2004.
“Electrical Motor Diagnostics for Generators Part 1: The
Basics,” ALL-TEST Pro, 2005
“Electrical Motor Diagnostics for Generators Part 2: Case
Studies,” ALL-TEST Pro, 2005
|